BKMYB - BATTERY ELECTRIC STORAGE,WET

  • MSDS: BKMYB
  • Manufacturer: GNB INCORPORATED
  • Product Name: BATTERY ELECTRIC STORAGE,WET
  • National Stock Number: 6140-00-438-0299
Product Identification

Product ID:BATTERY ELECTRIC STORAGE,WET
MSDS Date:01/03/1990
FSC:6140
NIIN:00-438-0299
MSDS Number: BKMYB

Responsible Party
GNB INCORPORATED
1110 HIGHWAY 110
MENDOTA HEIGHTS, MN 55118
US

Emergency Phone: 612-681-5000(75) (NANCY)

Info Phone: 612-681-5000/FAX -5143 (NANCY)

Cage: OMM77

Contractor
GNB INCORPORATED
43140 MENDOTA HEIGHTS, MN 55118 US

Telephone: 612-681-5000

Cage: OMM77

Ingredients

LEAD (SARA III)

CAS: 7439-92-1

RTECS: OF7525000

Fraction By Weight: 50%

OSHA PEL 0.05 MG/M3;1910.1025

ACGIH TLV: 0.15 MG/M3;DUST 9192

EPA Report Quantity: 1 LB

DOT Report Quantity: 1 LB


SULFURIC ACID (SARA III)

CAS: 7664-93-9

RTECS: WS5600000

Fraction By Weight: 27%

OSHA PEL 1 MG/M3

ACGIH TLV: 1 MG/M3; 9192

EPA Report Quantity: 1000 LBS

DOT Report Quantity: 1000 LBS

Hazards

Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Health Hazards Acute and Chronic:ACUTE-STINGING AND BURNING SENSATION
TO SKIN & EYES.CHRONIC-NOT GIVEN.
Effects of Overexposure:SEE HEALTH HAZARDS SECTION.
Medical Cond Aggravated by Exposure:EXPOSURE TO SULFURIC ACID MIST MAY
CAUSE LUNG DAMAGE AND AGGRAVATE PULMONARY CONDITIONS.

First Aid

First Aid:SEE A DOCTOR.EYES/SKIN:FLUSH WITH WATER FOR 15
MINUTES.INHALATION OF SULFUR OXIDE:REMOVE TO FRESH AIR.DISCONNECT
BATTERIES & VENTILATE THE AREA.INGESTION:DRINK LARGE QUANTITIES OF
MILK/WATER,FOLLOWED BY MILK OF MAGNESIA(NO CARBONATES),BEATEN EGGS
OR VEGETABLE OIL.SEE DOCTOR IMMEDIATELY.

Fire Fighting

Extinguishing Media:DRY CHEMICAL.
Fire Fighting Procedures:WEAR FIRE FIGHTING PROTECTIVE EQUIPMENT AND A
FULL FACED SELF CONTAINED BREATHING APPARATUS. EVACUATE AREA.
Unusual Fire/Explosion Hazard:WHEN ON CHARGE AND APPROACHING FULL
CHARGE, GASES GENERATED ARE FLAMMABLE. KEEP SOURCES OF IGNITION
(SPARKS & FLAMES) AWAY.

Accidental Release

Spill Release Procedures:APPLY AN EQUAL AMOUNT OR BAKING SODA, SODA
ASH, CAUSTIC SODA OR EQUIVALENT OVER SPILLED ELECTROLYTE TO
NEUTRALIZE IT AND ADD WATER IF NECESSARY TO FORM A SLURRY. SCOOP UP
SLURRY.
Neutralizing Agent:LIME OR SODA

Handling

Handling and Storage Precautions:STORAGE-STORE WITH VENT SIDE UP.BE
CERTAIN VENTS ARE FREE OF DIRT TO INSURE AIR FLOW.
Other Precautions:DO NOT SHORT OUT POSITIVE AND NEGATIVE ELECTRODES
WITH A CONDUCTOR. THIS MAY CAUSE A HOT ELECTRICAL SPARK.

Exposure Controls

Respiratory Protection:USE NIOSH-APPROVED RESPIRATOR IF 1 MG/M3 TWA IS
EXCEEDED (ACID).
Ventilation:LOCAL EXHAUST AT CHARGING STATIONS
Protective Gloves:RUBBER
Eye Protection:SPLASH-PROOF SAFETY GOGGLES/FACE SHIELD
Other Protective Equipment:RUBBER APRON AND BOOTS.EYES WASH STATION AND
SAFETY SHOWER. USE ACID-PROOF CLOTHING FOR MAJOR SPILLS.
Work Hygienic Practices:WASH THOROUGHLY AFTER HANDLING.
Supplemental Safety and Health
FOR ELECTROLYTE (SULFURIC ACID), SEE P/N B SAME NSN.

Chemical Properties

HCC:C1

Stability

Stability Indicator/Materials to Avoid:YES
NOT GIVEN.
Stability Condition to Avoid:HIGH HEAT, OPEN FLAMES

Disposal

Waste Disposal Methods:DO NOT DISPOSE OF BATTERY. SPENT OR UNUSABLE
BATTERIES SHOULD BE RECYCLED BY A LICENSED BATTERY RECYCLER.

Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.